MFT Two-Wire Flow Transmitter
Unique Features
- Non-contact sensor electronics
- Electronic signal conditioning circuit
- Digital flow rate and total indication
- Proportional analog output - Two-Wire
- Specific gravity compensation (all-fluids)
- Viscosity compensation (petroleum-based fluids)
- Pressure and temperature compensation (pneumatic applications)

Typical Flow Applications
- Pump flow output
- Compressed Air Consumption
- Cooling flow monitoring
- Combustion gas metering
- Steam flow useage/optimization

Description
The MEMFlo Flow Transmitter (MFT) is a state-of-the-art, microprocessor based two-wire transmitter with 4-20mA/ 0-5Vdc output, digital flow rate and total flow display. It combines our time-proven variable area technology with a high tech processor and solid state circuitry.
The MEMFlo Flow Transmitter (MFT) is sealed against industrial contamination by a NEMA 4, 12,13 (IP 57/52/54) rated enclosure and is available for either liquid, gas or steam service. The MFT is capable of calculating and displaying both flow rate and total accumulated flow. The flow rate and total flow can be displayed in any of the user selectable measurement units. The monitor's large 8 digit numeric LCD makes extended range viewing practical. The second 8 character alphanumeric display provides for selectable units viewing in RUN mode and prompts for variables in PROGRAM mode.
All MFT's come pre-calibrated from the factory. However, the unit may be adjusted by the user to meet specific system requirements. Calibration parameters are included for:
- Specific gravity compensation (all fluids)
- Viscosity compensation (petroleum-based fluids)
- Pressure and temperature compensation (pneumatic applications)
All meters include an analog output that can be configured for 0-5 Vdc, 0-10 Vdc, or 4-20 mA current loop.

Specifications
Enclosure Rating: NEMA 12 & 13 (equivalent to IP 52/54)
Operating Temperature: Fluid: -20°F to 240°F (-29°C to 116°C), Ambient: -20°F to 158°F (-29°C to 70°C)
Environmental: Humidity: 0-90% non-condensing
Accuracy: +/-2% of full scale
Repeatability: 0/5%
Electrical Power Requirement: 0.5 VDC Output 10-30 VDC @ 0.75 maximum, 0-10 VDC Output 12-30 VDC @ 0.75 maximum, 4-20 mA Output loop-powered, 30 VDC maximum
Power Consumption: 25 mA maximum
Analog Outputs: 0-5 VDC and 0-10 VDC into 10,000 Ohms minimum: 4-20 mA into 1000 Ohms maximum
Circuit Protection: Reverse polarity and current limiting
Transmission Distance: 4-20 mA limited by cable resistance: 0-5 VDC 1000 feet (300 m) maximum: 0-10 VDC 1000 feet (300 m) maximum
Isolation: Inherently isolated from the piping system
Rate and Totalization Display: Fixed or toggle modes of operation for rate and totalizer display: 8 digit, .70" high numeric display for rate and total: 8 digit, .35" high alphanumeric display for units and setup
Temperature Drift: 50 ppm/ C (Max)
Analog Output: Resolution: 1:4000
Transient Over-Voltages: Category 3, in accordance with IEC 664